Power supply voltage 100 to 240 VAC, 50/60 Hz Operating voltage range 85% to 110% of rated supply voltage
Power consumption 3.5 VA Sensor input
Models with thermocouple inputs
Thermocouple: K, J, T, R, or S Models with platinum resistance thermometer inputs
Platinum resistance thermometer: Pt100
Control
output
Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA Voltage output
(for driving
SSR)
Output voltage: 12 VDC 25%/15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Alarm output (See note.) SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
Control method ON/OFF control or 2-PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and individual indicators
Character height: E5CSL: 21.7 mm, E5CWL: 16.2 mm (PV), E5EWL: 20 mm (PV)
Other functions Temperature input shift, run/stop, protection functions, etc.
Ambient operating
temperature 10 to 55C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65C (with no icing or condensation)