Range | Easy TeSys |
---|---|
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Device short name | LC1E |
contactor application | Motor control Resistive load |
utilisation category | AC-1 AC-3 |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 32 A (at <55 xss=removed> 50 A (at <60 xss=removed> |
[Uc] control circuit voltage | 220 V AC 50 Hz |
Motor power kW | 7.5 kW at 220...230 V AC 50/60 Hz 15 kW at 380...400 V 15 kW at 415 V 15 kW at 440 V 18.5 kW at 500 V 18.5 kW at 660...690 V |
---|---|
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 50 A (at 55 °C) |
Irms rated making capacity | 320 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 256 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 260 A 40 °C - 10 s for power circuit 138 A 40 °C - 60 s for power circuit 60 A 40 °C - 600 s for power circuit |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit |
Average impedance | 2.5 mOhm - Ith 50 A 50 Hz for power circuit |
Power dissipation per pole | 2 W AC-3 5 W AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
Overvoltage category | III |
Pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Mechanical durability | 8000000 cycles |
Electrical durability | 1000000 cycles AC-3 350000 cycles AC-1 |
Control circuit type | AC at 50 Hz |
Control circuit voltage limits | 0.85...1.1 Uc (55 °C):operational 50 Hz 0.3...0.6 Uc (55 °C):drop-out 50 Hz |
Inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C) 95 VA 60 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C) 8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation | 2…3 W for control circuit |
Operating time | 12...22 ms on closing 4...19 ms on opening |
Maximum operating rate | 1800 cyc/h 60 °C |
Connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm?2; - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm?2; - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm?2; - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm?2; - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm?2; - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm?2; - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1.5…6 mm?2; - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1.5…6 mm?2; - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1…6 mm?2; - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…4 mm?2; - cable stiffness: flexible with cable end |
Tightening torque | Control circuit: 1.2 N.m Power circuit: 2.1 N.m |
Auxiliary contact composition | 1 NO |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Insulation resistance | > 10 MOhm for control circuit |
Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
mounting support | DIN rail Plate |
Standards | IEC 60947-4-1 IEC 60947-1 IEC 60947-5-1 |
---|---|
product certifications | EAC CE |
IP degree of protection | IP2X conforming to IEC 60529 |
Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
Permissible ambient air temperature around the device | -20…70 °C at Uc -60…80 °C storage -5…55 °C operation |
Operating altitude | 3000 m without derating |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical robustness | Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms) |
height | 84 mm |
Width | 56 mm |
Depth | 86 mm |
Net weight | 0.45 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 8.6 cm |
Package 1 Width | 8.4 cm |
Package 1 Length | 5.6 cm |
Package 1 Weight | 449 g |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 24 |
Package 2 Height | 15 cm |
Package 2 Width | 30 cm |
Package 2 Length | 40 cm |
Package 2 Weight | 11.184 kg |